Product Quick Selection Wheel

CAMTEC - 60W Power Supply HPW00601LIRC SERIES

Features
  • 60W Power Supply
  • -15°C...+75°C with active PFC
  • -15°C...+60°C full output power
  • Free air convection
  • Up to 86% efficiency
  • Active Inrush Current Limiter 700mA peak
  • Continuous short circuit protected
  • Overload & low voltage protected
  • EMI/EMS EN61000-6-2.3. EN55022 class B
  • cUL60950/16950 IEC(EN)60950-1
  • High reliability. shock & vibration proof

HPW00601LIRC SERIES

Product Overview

CAMTEC - HPW00601LIRC SERIES 

DIN Rail 60 Watts Power Supply 

Available Outputs:   12V,  24Vdc  

Description   The HPW power supply series realizes high power efficiency in a space-saving housing. Latest generation electrical devices relate to the high reliability of all Camtec products. The HPW60 is designed for operation under critical ambient temperature conditions in traffic signs and outdoor control units. The extreme low inrush of 495mArms allows easy multi array installations in large LED-signs or on UPS buffered systems. The power supply is equipped with an active PFC. The EMC harmonics allow low interferences of a larger number of HPW units to be installed into a single AC bus.

Parallel & series connection:   Camtec power supplies of the same model and the same output voltage can be either used in parallel or in series connection. The assembling of external parts is usually not recommended. Make sure that the output voltage of each connected unit is ±1% equal. We recommend connecting the DC-outputs to a neutral point or a power bar. Always use equal cabling length for all DC-outputs.

Control type   The power supplies accurately works down low output voltages down to 0V. Thereby the switching frequency is absolute stabile. The output response is linear to the input signal.

Power Good Relay:   As a standard the power good relay allows to control the power supply is ok. When the output voltage breaks down the contact opens. Galvanic isolation 60vdc..

Specifications

OUTPUT
Rated DC Voltage 24V 48V
Rated DC Current 2.5A 1.25A
Ripple [mVpp] 230Vac 20 (20MHz) 40 (20MHz)
Output adj. Range [V] 22,5...28,5V 40,5V...50,7V
Stability at load switch ± 0,5% ± 0,5%
GENERAL
AC Input Voltage 90-265Vac
Frequency 47-63Hz
DC Input Voltage 120-375Vdc
Input Current

230Vac <800mA

115Vac <1.6A

Load regulation < ± 0.1% 10-100%, 100-10%
Baseload Idling proof
Efficiency 86% typ.
Hold Up Time > 50ms 230Vac @ full load
Inrush Current < 700mApeak / 495mArms active electronic limiter for 1A CB-A
Soft Start 50ms typical
Power Good Relay <48Vdc/500mA, galvanic isolation 60Vdc
RELIABILITY

Over Current Protection

I(AB)

1.1x Irated
Over Voltage Protection 130% of Uout , auto recovery
Short Circuit Protection Continuous
Air & Creep Distance > 8mm
Input / Output Isolation I/P-O/P:3kVac I/P-G:2kVac O/P-G:1.4kVdc
MTBF EN61709 600000h
MTTF EN61709.SN29500 157680h @ 40°C 24/7, 85% load
Lifetime expected 18 years under 24/7 40°C 85% load conditions
STANDARDS AND APPROVALS
Safety EN60950-1, EN60204-1

Safety Class

(with PE connected)

1, VDE0805, VDE0100, IP20
EMI EN55022 class B / EN61000-3-2 (harmonics)
EMS EN61000-6-2, EN61000-6-3 (noise immunity)
MECHANICAL
Dimensions (HxWxD) 124x50x99.5mm
Weight 700g

Selection Table

MODEL HPW00601.24T HPW00601.48T
Rated DC Voltage 24Vdc 48Vdc
Nominal Current 8.0A 5.0A

Notes:

AC Input Connector: 3pole terminal connector LS7,5mm AWG26-AWG12,

DC Output Connector: 2pole terminal connector LS5,08mm AWG26-AWG12,

Technical Illustration

  • CONNECTIONS CONNECTIONS
  • TEMPERATURE DERATING TEMPERATURE DERATING
  • ELECTRICAL SAFETY ELECTRICAL SAFETY
  • ORDERING ORDERING
  • COATING OPTION COATING OPTION
Back to Top

Ask Your Question