Product Quick Selection Wheel

DRP 24V 2PH Series DRP 24V 2PH - Delta 2 Phase AC/DC DIN Rail

Features
  • 24VDC 120W - 240W
  • Designed for single phase input 180-305Vac (for L-N) or
  • 2 of 3 Phase system 2 x 180-550Vac (for L-L) or 244-780Vdc
  • Compact and corrosion resistant aluminum casing
  • High efficiency > 90%
  • Power boost of 120% for 3 seconds
  • Built in constant current and hiccup during overload protection
  • Built in DC OK Contact
  • MTBF > 500 000hrs
  • Wide operating temperature range from -30C to +70C
  • Conformal coating on PCB to protect against chemical & dust pollutants
  • Overvoltage / Overcurrent and Over Temperature protection

DRP 24V 2PH - Delta 2 Phase AC/DC DIN Rail

Product Overview

 

Delta Electronics CliQII 24Vdc 2 Phase DIN Rail Power Supplies

The CliQ II DIN rail power supply series with a new model offering two phase 2 x 180-550Vac (for L-L) or single phase 180-305Vac (for L-L) for 24V/5A abd 24V/10A outputs.  The DRP24V120W2BN and DRP24V240W2BN has safety approvals for single phase and two phase input according to IEC/EN/UL 60950-1 and UL508 safety standards.  The product features wide AC input voltage for single or two phase range.  Such feature can protect the power supply from damage when user accidentally apply two phase input on the single phase power supply connection.  The product performs under wide operating temperature form -30C to +70C with 2-Phase and 3-Phase application (for L-L) . Conformal coating is applied on the PCB assembly to protect against dust and chemical pollutatn to withstand harsh industrial environments.  Other major safety approvals included.

Specifications

OUTPUT
Output Model DRP024V120W2BN DRP024V240W2BN
Output Voltage 24Vdc 24Vdc
Output Voltage Range 24V - 28Vdc 24V - 28Vdc
Output Current 5A 10A
Output Power 120W 240W
Power Boost 120% 5 Secs 120% 5 Secs
Rise Time <70ms at nom input, 100% load <100ms at nom input, 100% load
Start up Time 2.5s at nom input, 100% load 1s at nom input, 100% load
MTBF >500,000 hrs >500,000 hrs
Hold-up Time

> 10ms at 2 x 230Vac  100% load

> 50ms at 2 x 400Vac  100% load

> 18ms at 2 x 230Vac  100% load

> 18ms at 2 x 400Vac  100% load

Indicator Green LED (DC OK)
Alarm DC Ok Relay (NC)
Line Regulation < 0.5% typ. at 100% load
Load Regulation < 1% typ. at 100% load
PARD (20MHz) < 150mVpp
INPUT
Output Model DRP024V120W2BN DRP024V240W2BN
Phase Input Two Phase Two Phase
Input Voltage

2 x 180-550VAC (2-Phase)

2 x 180-550VAC (2-Phase)

Input Frequency 47-63Hz 47-63Hz
DC Input Voltage 254-780Vdc 254-780Vdc
Efficiency  > 90.0%  at 100% load > 90.0%  at 100% load
Input Current

< 1.2A @ 2 x 230Vac

< 0.65A @ 2 x 400Vac

< 1.5A @ 2 x 230Vac

< 1.0A @ 2 x 400Vac

Power Factor Conform to EN61000-3-2 >0.84 @2 x 230Vac & 400Vac
Max Inrush Current <50A @ 2 x 200Vac & 500Vac <50A @ 2 x 200Vac & 500Vac
Leakage Current < 3.5mA < 3.5mA
ENVIRONMENTAL
Operating Temperature -30°C to +70°C
Storage Temperature -40°C to +85°C
Power De-rating

DRP120:  > 60°C de-rate power by 4% / °C

DRP240:  > 50°C de-rate power by 2% / °C

Vertical Mounting

Operating Humidity 5 to 95% RH (Non condensing)
Operating Altitude 0 – 2,000 m
PROTECTIONS
Overvoltage 32V, +/-10% SELV Ouput, Hiccup Mode, Non-Latching (Auto-Recovery)
Overload/Overcurrent > 120-160% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery)
Over Temperature  < 80C Surrounding Air Temperature @ 100% load, Non-Latching (Auto Recovery)
Short Circuit Hiccup Mode, Non-Latching (Auto-Recovery) when the fault is removed)
Degree of Protection IP20
Protection against shock Class 1 with PE (Primary Earth) connection
Galvanic Isolation

Input to Output 4.0KVAC

Input to Ground 2.0KVAC

Output to Ground 1.5KVAC

STANDARDS
EMC / Emissions CISPR22, EN55022, CISPR 11, EN55011, FCC Title 47: Class B
Safety SIQ to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1
Industrial Control Equipment UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Electrical Equipment In Power Installations: EN 50178 / IEC 62103
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC.
Materials & Parts RoHS Directive 2011/65/EU Compliant
MECHANICAL
Output Model DRP024V120W2BN DRP024V240W2BN
Case Cover Aluminium Aluminium
Dimensions 124L x 40W x 117H mm 124L x 60W x 117H mm
Weight 0.62kg 0.81kg
Cooling System Convection Convection
Input Terminal 3 Pins (600V/35A) 3 Pins (600V/35A)
Input Wire AWG 18-8 AWG 18-8
Output Terminal 4 Pins (300V/28A) 6 Pins (300V/28A)
Output Wire AWG 18-12 AWG 16-12
Mounting Rail TS35 DIN Rail TS35 DIN Rail

Selection Table

MODEL NUMBER

Output

Voltage

Output

Current

 Power Boost

( 3 Secs)   

Output

Power

                          

DRP024V120W2BN

24Vdc

5A 6A 120W  
DRP024V240W2BN

24Vdc

10A 15A 240W  

Technical Illustration