Product Quick Selection Wheel

PSC06 SERIES Battery Chargers - 2U ULTRA COMPACT

Features
  • 1000W - 6000W
  • Configurable Battery Charging System
  • 2U 19" Rack Mounting
  • Network Monitoring
  • N+1 Operation
  • Fully Featured Telecom Grade Rectifier

Battery Chargers - 2U ULTRA COMPACT

Product Overview

 

DC Power System ideal for Telecoms and Data Networks

Enatel’s PSC06 2U Ultra Compact Rectifier systems are configured using Enatel’s state of the art high frequency switch mode rectifier modules and intelligent network capable controllers.

They include built-in load and battery distribution, AC input isolation and suppression all in a 2U 19” rack mountable power shelf and can be customized and configured to individual customer requirements..

Specifications

input
AC input 240V AC (90-300V) Single phase or 415V AC Three phase (shelf type dependant)*
Frequency range 45-66 Hz
Power factor >0.99 full load
Termination Single phase, 6 - 10mm² L, N, E tunnel terminals* Three phase, 6 - 10 mm² L1,L2,L3,N,E terminals * (Single phase by linking line terminals)
dc outputt
Nominal voltage 48V (+48V or +24V optional)*
Rated system output power 6-8k Watts @ -48V (refer to table) 3-4k Watts @ 24V
Polarity Positive earth, (negative earth option available)*
dc distribution
Load Standard Shelf configuration. (Customized configuration available)*
Battery Standard Shelf configuration (Customized configuration available)*
Breaker fail detection Electronic fail detection on both load and battery breakers
DC terminals Rear Connect DIN Rail
Load Tunnel terminals 6 mm² to 16mm²*
Battery Tunnel terminals 35mm²*
Low voltage disconnect See Standard Shelf configuration.
ENVIRONMENTAL REQUIREMENTS
Ambient Temperature -20ºC to +70ºC
Storage Temperature -30ºC to +85ºC
Humidity 5-95% RH (non-condensing)
Altitude <2,500m at full power
MECHANICAL

Dimensions

W, H, D

482.6mm (19” mount), 89.0mm (2U), 390.0mm
Weight 9kg (excluding rectifier modules)

Shipping Dimensions

W, H, D

540.0mm, 150.0mm, 435.0mm

Shipping Weight

10.5kg (excluding rectifier modules)
MONITORING & CONTROL
Display Multi-lingual alpha numeric backlit display 
Communications

Serial: 1x USB port on front panel for local PC interface

TCP/IP: Ethernet interface for communication using SNMP protocol and internal web based configurator*

Modbus: Supported via TCP/IP*

LED Indicators

Green: Power on/monitor OK

Yellow: Non urgent alarm

Red: Urgent alarm

Audible 90dBA buzzer mappable to user defined conditions
Controls 3x push buttons for parameter setting or viewing on front panel
Signal Inputs

Serial bus for rectifier control and interface to peripheral modules

6x digital inputs

2x temperature sensors (one fitted by default)

Alarms 6x alarm relays, 5x of which can be mapped for customised alarm settings
Alarm Contacts 0.3A 100V volts free changeover contacts
Logging Capacity

Periodic log, 16,384 records (dependant on number of parameters logged)

Event log, 16,384 records (dependant on number of parameters logged)

Connections Relay outputs, mini combicon to accept 1.5mm² wire USB port, USB mini B
*TCP/IP and modbus options only available with SM36 supervisory module.
CONFIGURATION and OPTIONS

Rectifiers

RM2048XE: 2.0kW modular rectifier, 230V AC input, 48V DC output, 41.7A maximum output

RM2048HE: 2.0kW modular rectifier, 230V AC input, 48V DC output, 41.7A maximum output

RM2048/24: 2.0kW modular rectifier, 230V AC input, 48 or 24V DC output, 41.7A maximum output

RM1860/48: 1.8kW modular rectifier, 230V AC input, 60 or 48V DC output, 30.0A maximum output

Supervisory Modules

SM35: standard monitor featuring full temperature compensation, automated and manual battery testing/equalisation

SM36: enhanced monitor featuring full temperature compensation, automated and manual battery testing/equalisation with TCP/IP

ARBP-1M

Metal rectifier blanking panel

ASM-ABM24(-24-48-60)

Battery condition monitor for 24, 48 or 60V battery strings
 ASM-AC3P AC mains monitor

Selection Table

Model NumberMAX RECTIFIERSMAX SHELF POWERDC DISTRIBUTION
PSC06 V1    3

24, 48 or 60VDC

6.0kW

Positive or Negative Earth

6 x load circuit breakers (6-63A)

2 x battery circuit breakers (max 63A)

125A magnetically latching battery LVD

PSC06 V2    3

24, 48 or 60VDC

6.0kW

Positive or Negative Earth

16 x load circuit breakers (2-30A)

2 x battery circuit breakers (max 100A)

125A magnetically latching battery LVD

*System part numbers are dependent on configuration options. For final system part numbers consult our sales staff for configuration advice.

Technical Illustration

Back to Top

Ask Your Question