B500 SERIES B500 - Schaefer Euro Series Battery Charger

Features
  • 180-250W
  • Battery Charger Industrial Grade
  • Temperature Compensated
  • Auto and Manual Selection of Float
  • Equalize and Charge
  • Eurocassette Mounting
  • Wall Mounting
  • Chassis Mounting
  • DIN Rail Mounting

B500 - Schaefer Euro Series Battery Charger

Specifications

INPUT
Input voltage

1ph 115/230Vac

3ph 200/400/480Vac

See selection table

Units will turn off with under or over input voltage.

No-load input
power
3-6W model (series dependant)
Inrush current AC input limited by thermistor
Switch on time 1-2 seconds.
Input Options

Option au: Autoranging for 115/230Vac input

Option pr: Power OK via relay contacts

OUTPUT
Output voltage

Voltage range; 4.5 - 400Vdc

See selection table

Output current See selection table.
Ripple & noise 1% + 30mVpp
Line regulation 0.1% (±10%)
Load regulation 0.2% typical, load step 10-90%
Load transient 6% typical, load step 10-90%
Response time 2-3ms typical ±1%
Temperature coefficient 0.02% per °C typical.
Holdup time 10mS at 220VAC typical
Turn on rise time 100mS typical (soft start)
Remote sensing Standard for all series
Efficiency 80%-92% typical
Output Options

Option dd: Decoupling Diode for redundant / parallel operation

Option cs: Active Current Sharing

Option h: Remote on/off (inhibit)

Option dr: DC OK via relay contacts

Programming Options: See selection table

PROTECTION
Overload protection Current limited at 105%–110% of full load.
Overvoltage protection OVP switches off module with automatic return to operation
Protection Options

Option i: Inrush Current Limiting

Option sd: Reverse polarity protection for DC input by Series Diode

MTBF

100Khrs to 140Khrs at 40°C

acc. to MIL-HDBK-217E (notice 1)

ENVIRONMENTAL
Operating temperature

-20°C to +75°C

(optional -40 to 75C)

Load derating Derate 2.5% per °C, from +55°C to 75°C
Cooling

H: Heatsink - natural convection

F: Fan - increased airflow recommended

TF: Temperature controlled Fan included

See selection table

Environment Options

Option c: Extended temperature range to -40°C

Storage temperature -40°C to +85°C
Humidity Up to 95% RH, non-condensing
STANDARDS
EMI standards acc. to EN61000-6-4 class A, optionally class B
Immunity standards acc. to EN61000-6-2
C-Tick AS/NZS CISPR11: 2002 Group1 Class A
Safety / Construction acc. to EN60950-1 / EN50178
Protection category

IP20 acc. to EN60529

NEMA or others on request

MECHANICAL
Mounting

See technical illustrations

Eurocassette, pluggable module for 19" subrack

Option w: Wall Mounting

Option cha: Chassis Mounting

Option din: DIN Rail Mounting

Dimensions See Technical illustration
Connector

H15 acc. to DIN 41612 H15

and high current connectors for I > 50A,

or terminals / bolts / bars

Mechanical Options

Option ms: Increased Mechanical Strength

Option t: Tropical protection

19" Rack Mounting

Options

Subrack Height 3U, 5U, 6U

Wiring, Front Panels

Accessories: Fuses, MCBs, Mains on/off switch

Contact Powerbox for rack configuration

Selection Table

INPUT

115VAC

±20%

INPUT

230VAC

+15% -20%

INPUT

'115 ± 20%

230VAC + 15% -20%

INPUT

3x200VAC

+15% -20%

OUTPUT

AMPS

        

COOLING

HEATSINK

        

BATTERY 

CHARGER

VOLTAGE

 

VOLTAGE

ADJ RANGE

B561 B581 B591 B561V 16   H   12   12-16
B562 B582 B592 B562V 8   H   24   24-32
B564 B584 B594 B564V 4   H   48   48-64
B566 B586 B596 B566V 3.2   H   60   60-80
B567 B587 B597 B567V 2   H   110   110-145
B568 B588 B598 B568V 1   H   220   220-290

Cooling

H: Heatsink - natural convection

F: Fan - increased airflow recommended

TF: Temperature controlled Fan included

See selection table

 

Model configuration options:

Add the options to the model number, eg. B560-dd-dr-cs

Options for Input, Output, Environmental and Mechanical follow.

19" Rack Mounting Options

Subrack Height 3U, 5U, 6U

Wiring, Front Panels

Accessories: Fuses, MCBs, Mains on/off switch

Contact Powerbox for rack configuration

INPUT OPTIONS
Option “i” (inrush current limiting): A thermistor is connected in series with the input lines which changes its resistance from high to low when it gets hot. It does not reduce the current surge if the input power is interrupted for a short period of time not allowing the thermistor to cool down. Thermistors are fitted as standard to all mains input models except for 1-phase input of models > 2.5kW. Thermistors are available up to 45A. For higher input current an electronic inrush current limitation can be offered.
Option “ie” electronic inrush current limiting An electronic circuit limits the inrush current.
Option “sd” (series diode): A series diode protects the module against input voltage of wrong polarity (additional power losses).
Option “ad” (anti-parallel diode): To avoid the power losses of a series diode a diode is provided with opposite polarity in parallel to the input blowing an internal or external fuse if the module is connected to a supply with wrong polarity.
Option “au” (auto-ranging) For standard dual AC input models the range of 115/230Vac is to be selected by connecting the input line to different pins on the connector. With auto-ranging the unit senses the input voltage and provides automatically the correct connection.
Option “p” (power fail): A signal (logic or relay) is given if the input voltage (AC or DC) drops below the specified limit. In AC input units we sense the rectified input voltage so that a power fail alarm will not be triggered if at light loads mains power returns before the input capacitors are substantially discharged.
Option “r” (relay): A relay instead of a logic signal is provided for failure indication.
OUTPUT OPTIONS
Option “dd” (decoupling diode): For redundant operation the outputs of two or more units are paralleled behind de-coupling diodes so that an internal fault of one module does not affect the operation of the others. These diodes cause power losses.
Option “cs” (active current sharing): An additional control circuit provides active current sharing via an interconnecting wire between converters that operate in parallel. Active current sharing should be used for multi-output units operating in parallel.
Option “csi” (current sharing interrupt): Option "csi" will effect the removal of the "cs" signal. Should there be an instance where a unit is not supplying the load, then the effect of its "cs" signal is removed, and the load voltage is unaffected by this condition.
Option “h1” (inhibit): A terminal connected to the negative input line also shuts off the converter. This can also be used in conjunction with a thermal trip which shuts the unit down.
Option “h2” (inhibit): Operation of the unit is inhibited if a voltage signal (5V/10mA) is applied in reference to the negative line of the (main) output.
Option “rco” (reducing current limiting at over temperature) A circuit reduces the current limiting level at higher temperature (to be specified).
Option “d” (DC-ok, one output): A logic signal is given if the output voltage (main output in multi-output systems) is below the specified limit.
Option “m” (DC-ok, all outputs): In multi-output systems a logic signal is provided if the voltage of any output is below the specified limit.
Option “ac” (AC ok) A logic signal connected to relay contacts is given if the output voltage of an inverter is below the specified limit.
Option "y" (sys-reset): This logic signal is a combination of power fail and DC-ok as specified for VME systems.
Option "r" (relay): A relay instead of a logic signal is provided for failure indication.
CHARGER PROGRAMMING
Option "tc" Temperature compensated charging voltage(sensor not included)
Option "ts1" Temperature sensor, not interchangeable due to fixed resistor values
Option "ts2" Interchangeable, IC controlled
Option "ch1" Automatic selection of charging characteristic (float / equalize charge) with timer
Option "ch2" Additionally: Manual selection of charging characteristic
Option "ch3" Additionally: Boost charge operation (manually activated with
time delayed return to normal operation)
ENVIRONMENT OPTIONS
Option "t" (tropical protection):The unit is given additional protection by a heavy
coat of varnish on the printed circuit board(s) and components.
Option "c" (extended temperature range):The circuit is designed and tested for
operation at an ambient temperature as low as –40 °C.
Option "ms" (increased mechanical strength): Screws are secured by Locktite and
heavy components are fastened by ties and/or glue. Modules with the "ms" option
meet the standard EN61373 regarding shock and vibration.
MECHANICS OPTIONS
Standard mounting "Eurocassette" pluggable module for 19" sub-racks 8
Option "w" (wall mounting): Module is screwed against a mounting plate for
installation in a cabinet. The load connections are typically a terminal block.
Option "cha" (chassis mount) Module is designed for installation to a structure or
within cabinet. Screw type connectors are supplied with the module.
Option "din" (DIN rail mount) Module is designed for DIN rail mounting to a
structure or within Cabinet. Screw type connectors are supplied with the module.

Technical Illustration