Product Quick Selection Wheel

6000VA DC/AC INVERTER PREMIUM ODX-6000

Features
  • Sine wave output voltage
  • Suitable for motors control
  • Adjustable output frequency
  • Adjustable output voltage
  • High input-output isolation 3000Vrms
  • Remote off opto-coupled
  • Alarm by isolated relay contacts
  • Configurable input: Reverse or Mid power
  • Remote control via RS232
  • CAN BUS (optional)
  • Parallelable output (optional)
  • Railway version EN50155 (optional)
  • Fire and smoke: EN45545-2 approved

PREMIUM ODX-6000

Product Overview

The ODX-6000 consists of three phase sine-wave DC-AC inverters with galvanic isolation between input and output. The unit allows:

  • Changing the output frequency by means of DIP-switch-7 of SW1. OFF: 50Hz or default programmed, ON: 60Hz 
  • Change local/remote (waiting RS-232 commands) bymeans of DIP-switch-6 of SW1. OFF: local, ON: remote 
  • Shutdown applying voltage output 15 to 143V on pins 3 and 4 of J4 
  • Start-up motors by means of a soft start. In the start-up, the output voltage rises linearly from 0V to set voltage and the frequency from the initial to the set one. The start-up ramp slope may be changed via RS-232 
  • Set the rotation speed of a motor according to the appropriate Voltage/Frequency ratio.Configurable input (pin 1 and 2 of J4): 
    • Reverse mode: Changing the rotation direction for the next start-up of a motor by applying voltage between 15 and 143V. 
    • Mid power mode: Changing the output frequency in V/F mode from nominal to a mid-power frequency by applying voltage between 15 and 143V. 
  • Monitoring the status of the input and output voltage through the contacts of two separate solid state relays. 
  • Set and monitor parameters via RS-232. 

The ODX-6000 is equipped with a maximum average power protection as well as maximum output peak current protection. This protects the semiconductors even when an output short-circuit occurs. It also features a disable function for input under-voltage, which allows protecting the batteries from harmful discharges.

Specifications

INPUT
Input Voltage range -30, +25% Vin nom
Max input ripple 5% Vin nom (Vrms, 100Hz)
OUTPUT
Nominal Output Voltage  See table

Output voltage range:

20…100% of Von (adjust via remote control)

Output frequency

50 / 60Hz via DIP-switch,

5…75Hz via RS-232

Load regulation 

< 4 .5%

Line regulation

< 2% Vin -25% … +25%,

< 10% Vin -30% … +30%

Output wave distortion THD

< 2% (average of 16 samples)

 Output HF ripple

< 2.5%
ENVIRONMENTAL

StorageTemperature

-25 … 80°C

Operating temperature at Full load -25 … 55°C (EN50155 OT1)
Operating temperature at 62.5% load -25 … 70°C (EN50155 OT3)
Operating temperature at 25% load  -25 … 85°C (EN50155 OT5)
Relative humidity 5 … 95%
Cooling  Internal controlled internal fan
MTBF (MIL-HDBK-217-E; Gb, 25°C) 100.000 h
EMC

Emission according

EN61000-6-4, EN50121-3-2

Immunity according

EN61000-6-2, EN50121-3-2

SAFETY

Dielectric strength: Input /output

3000 Vrms / 50Hz / 1min

Dielectric strength: Output / ground

1500 Vrms / 50Hz / 1min 

Dielectric strength: Input / ground

500 Vrms / 50Hz / 1min

Safety according to

EN60950-1, EN62368-1

Fire and smoke

EN45545-2 approved

MECHANICAL

Approximate weight

<8950 g

Shock and Vibrations according to

EN61393:2011 Category 1 Class B

Protection degree

IP20

CONTROL

OutputOk LED

Green 

Input OK LED

Green

Input alarm

Open when alarm. Maximum rating: 0.16A at 160Vdc

Output alarm

Open when alarm. Maximum rating: 0.16A at 160Vdc

Remote OFF input

OFF: applying 15…143Vdc, Impedance>35kΩ

Configurable input

(reverse or mid-power)

ON: applying 15…143Vdc, Impedance>35kΩ

PROTECTIONS

Against overloads

Current and I²T limited (see overload protection)

Against over temperature

Shutdown with auto-recovery

Selection Table

 

 

INPUT

VOLTAGE

DC

(V)

INPUT

VOLTAGE

RANGE

(V)

MAX.

INPUT

CURRENT

(A)

OUTPUT

VOLTAGE

AC

(V)

OUTPUT

CURRENT 

(A) 

ACTIVE

OUTPUT

POWER

(W)

APPAR.

OUTPUT

POWER

(VA)

OUTPUT

PEAK

CURR. 5 S

(rms) 

(A)

OUTPUT

PEAK

CURR.

10MS

(Iopk) 

(A)

EFFICI

(%)

NO LOAD

INPUT

CURRENT

(A)

ODX~6000~7502

24 16.8 - 30 232 400 6.50 3500

4500

7.8A

20

91.0

1.70

ODX-6000-7503

24 16.8 - 30 294 400 8.66 4500

6000

9.7A

20

91.0

1.70

ODX-6000-7505

48 33.6 - 60 191 400 8.66 6000

6000

11.5

20

93.6

0.85

ODX-6000-7506

72 50.4 - 90 127 400 8.66 6000

6000

11.5

20

94.3

0.58

ODX-6000-7507

110 77 - 138 83 400 8.66 6000

6000

11.5

20

94.2

0.38

Technical Illustration

Back to Top

Ask Your Question